Inside the Crossroads Proposal: What the County’s Posted Documents Explain

By John L. Williams
Editor, The Spotsylvania Gazette

SPOTSYLVANIA COUNTY, Va. — The documents posted on Spotsylvania County’s website for Crossroads Technology Campus describe more than buildings. They outline proposed buffers, cooling-water arrangements, vehicle access, stormwater planning and noise controls.

The materials are part of special use permit application SUP26-0003. They include the applicant’s narrative, development plans and supporting studies. Their appearance on the county website does not make every prediction a county finding or every proposed feature a final approval.

Land, buffers and building height

The applicant’s narrative describes a 555.05-acre property and proposes approximately 349.5 acres—63 percent—as open space. Open space does not automatically mean public access.

It describes 300-foot vegetated buffers beside residential properties and 400-foot building setbacks. A buffer provides separation and screening; a setback controls building placement. These overlapping distances should not be added together as 700 feet.

Required access roads and utilities could enter the buffers. The proposed building-height limit is 75 feet. These specifications alone do not establish what would be visible from individual homes.

Building space and development phases

The phasing plan attached to the traffic memorandum identifies approximately 750,000 square feet of data center floor area in the first phase and 1,358,500 square feet in a future phase—a combined 2,108,500 square feet.

Floor area measures space inside buildings, rather than the entire property or necessarily the buildings’ ground footprint. Roads, substations, drainage facilities and buffers occupy other portions of the site.

Noise predictions and proposed limits

Ramboll’s August 20 sound study predicts full-cooling-load levels of 32–45 dBA and 51–60 dBC at evaluated locations, concluding that its modeled results meet the proposed standards.

The two measurements capture different sound characteristics: dBA approximates typical human hearing sensitivity, while dBC retains more low-frequency sound.

The proposed residential-boundary limits quoted in the study are 50 dBA/65 dBC during daytime and 45 dBA/60 dBC overnight. The model assumes sound-control measures, including silencers and generator enclosures. These are predictions rather than measurements of an operating campus.

A difference between the posted documents

The sound report references a July layout with eight buildings on approximately 633 acres. The applicant’s later narrative describes a 555.05-acre property.

That difference warrants clarification about whether the noise modeling applies to the revised layout. It does not, by itself, establish that the conclusions are incorrect.

Backup generators

The sound study says detailed testing schedules were unavailable and estimates approximately 3.8 testing hours per generator annually. It describes exemptions for testing, maintenance and emergency operations.

The report also states that final equipment selections and acoustic treatments remain subject to change.

Traffic and access

The August 26 traffic memorandum evaluates the first phase, with primary access from Eagle Drive through Lee Hill School Drive and Route 17.

It estimates 743 daily vehicle trips, including 83 during the morning peak hour and 68 during the afternoon peak. An arrival and departure count as separate trips.

The memorandum concludes that this phase falls below the traffic-study thresholds it identifies and does not warrant a separate left-turn lane at the proposed entrance. Those conclusions address the first phase, not the completed campus.

Cooling water

The narrative describes a conditional allocation of 1 million gallons of reclaimed water daily for cooling. An allocation is not a measurement of actual consumption.

The applicant says drinking water would serve domestic uses but would not supply industrial cooling.

Wetlands and drainage

The applicant acknowledges wetlands, floodplain and Resource Protection Areas on the property. Proposed impacts would require additional review and applicable approvals.

The phasing plan identifies stormwater management for each phase at the site-plan stage. That means the proposal anticipates drainage facilities, while their detailed design remains part of subsequent planning.

Understanding the maps

The county’s project page provides an illustrative plan, an updated development plan and a separate viewshed analysis. Each serves a different purpose: showing the overall concept, documenting development details or examining visibility.

An overhead illustration helps readers understand the layout, but it cannot alone establish what a particular household would see. That requires attention to terrain, viewing location, building elevations and screening.

Map and document source: Spotsylvania County Planning & Zoning, Crossroads Technology Campus application, SUP26-0003⁠.